NT-348/A
One-Circuit Track, Live End Feed with Circuit Limiter
Powers track system from the end of a run. Includes two knockouts and can be utilized on hard, grid ceilings, or pendant suspended track. Current Limiter can be used as an on/off switch. Breaker features a “tripped” condition indicator.
Why and when to use a Nora Current Limiter?
Use Nora’s track current limiter in tough watts per square foot. Commercial, residential and NEC calculate the wattage of a line voltage track run by the length of the run, not by the wattage consumed. NEC applies 45 watts per foot regardless of actual load.
Example: (3) 39W Fixtures on a 20′ run would be calculated at 900W (20′ at 45 Watts)
With Nora’s 1 amp current limiter track feed, this run is now limited to 120 watts. A savings of 780 watts in the watts per square foot.
Downloads
Additional information
Compatibile Track Systems | |
---|---|
Finish | |
Accessory Type |